PermAlert
Leak Detection / Location Sensor Cables,
Probes and Float Switches

Water Based and Hydro/Chemical Sensor Cables
1.AGW -
detects water based and hydrocarbon liquids
2.AGW-GOLD
- detects highly corrosive liquids
3.AGT
- detects water based and hydrocarbon liquids
4.AGT-GOLD
- detects highly corrosive liquids
Hydrocarbon
Sensor Cables
1.TFH
- detects only hydrocarbons
2.TFH-GOLD
- detects only hydrocarbons
Probes
and Float Switches
1.PWS
- water liquid probe
2.PHL
- liquid hydrocarbon probe
3.PHFW
- monitor well probe
4.PHFW-M
- monitor well probe
5.PFS
- float switch
6.PSTV
- float switch
7.PTHL
- high level float switch
For
information about our preinsulated piping systems, visit
the Perma-Pipe/Ricwil Piping Products page.
For information about our secondary contained piping systems,
visit the PermAlert Piping Products page.
To view and download our product guide specifications
and autocad detail drawings, view the Guide Specifications
and Drawings page.
Water Based and Hydro/Chemical Sensor Cables
1.AGW
AGW is a quick drying cable that will detect water based
and hydrocarbon liquids. This cable is corrosion resistant
for most applications and is used in secondary contained
pipes and flat floors.
Specifications
Sensor cable shall detect water-based, chemical and hydrocarbon
liquids. The cable can be flushed and dried in place and
will not require replacement after a leak event of any
volatile liquid. Tha cable shall have a breaking strength
of at least 100 pounds (45Kg).
2.AGW-GOLD
AGW-GOLD is a quick drying cable that is chemically resistant
and designed to detect highly corrosive liquid leaks such
as acids, bases and solvents. Typical applications are
secondary contained pipes in chemical installations, sub
floors of clean room manufacturing areas, and high temperature
applications such as steam pipe containement systems.
Specifications
Sensor cable shall be of fluoropolymer and polymer coated
wire construction with no exposed metal parts. Cable shall
detect water-based, chemical and hydrocarbon liquids.
The sensor cable can be flushed and dried in place and
will not require replacement after a leak event of any
volatile liquid. The cable shall have a breaking strength
of at least 100 pounds (45Kg) and shall be resistant to
corrosion, abrasion, and most chemicals tested in accordance
with exposure procedures in ASTM D-543.
3.AGT
AGT is a wicking cable specially designed for the leak detection
of water-based and hydrocarbon accumulations at a shallow
depth of 1/16" (2mm) of liquid in subfloor or other
flat surface leak monitoring applications. This cable requires
more drying time than AGW and is corrosion resistant for
most applications. AGT can be strapped to above ground single-wall
pipes.
Specifications
Sensor cable shall detect accumulations of water based
and hydrocarbon liquids at a shallow depth of 1/16"
(2mm) in subfloor or other flat surface applications.
The cable shall be capable of being flushed and dried
in-place and will not require replacement after exposure
to any compatible or volatile liquid. The cable shall
have a breaking strength of at least 100 pounds (45Kg).
4.AGT-GOLD
AGT-GOLD is a wicking cable that is chemically resistant
and designed to detect highly corrosive acid, base, and
solvent leaks in clean rooms, sub floors, above-ground single-wall
pipes, and equipment applications. Like AGT, this cable
requires more drying time than AGW.
Specifications
Sensor cable shall be of fluoropolymer and polymer coated
wire construction with no exposed metal parts. Sensor
cable shall detect accumulations at shallow depth of 1/16"
(2mm) and be resistant to most acids, bases and solvents
and be capable of being flushed and dried in place. The
cable will not require replacement after a leak event
of any compatible and/or volatile liquid. The cable shall
have a breaking strength of at least 100 pounds (45Kg)
and shall be resistant to corrosion, abrasion, and most
chemicals tested in accordance with exposure procedures
in ASTM D-543.
Hydrocarbon
Sensor Cables
1.TFH
TFH is a wicking cable specifically designed to detect
only hydrocarbons. This cable may be direct buried to
a maximum depth of 20 feet (6m) to locate fuel leaks while
ignoring the presence of water. This cable is ideal for
monitoring single-wall pipes and tanks.
Specifications
Sensor cable is designed for direct burial to a maximum
depth of 20 feet (6m). The cable shall be reusable, when
dried, after exposure to gasoline or other volatile hydrocarbon
liquid.
2.TFH-GOLD
TFH-GOLD is a wicking cable specifically designed to detect
only hydrocarbons and be installed in corrosive applications.
Applications include locations where hydrogen sulfide
or other corrosive gases or liquids may be encountered,
such as refineries and oil fields.
Specifications
Sensor cable shall have no exposed metal to vapors and/or
liquids. The cable shall detect only hydrocarbons while
ignoring water and water-based liquids. The cable is designed
for direct burial to maximum depth of 20 feet (6m) and
capable of providing a response time of not more than
4 minutes to most hydrocarbon liquids without losing its
corrosion resistance.
Probes
1.PWS - Water based liquid probe
The PWS probe can easily be connected into a PAL-AT "sensor
string" providing increased utilization of the PAL-AT
capabilities. Each probe assembly includes a probe integrator
with 60 feet (18m) of jumper cable to connect to the sensing
string, and 20 feet (6m) of lead cable to attach the probe
to the probe integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at the probe. Its solid-state
stainless-steel construction allows the PWS probe to respond
to all conductive liquids - water, acids, bases, chemicals,
etc. The probe resets quickly after resets quickly after
removal from the liquid.
2.PHL
- Hydrocarbon liquid probe
The PHL probe can easily be connected into a PAL-AT cable
"sensing string" providing increased utilization
of the PAL-AT capabilities. Each probe assembly includes
a probe integrator with 60 feet (18m) of jumper cable
to connect to the sensing string, and 20 feet (6m) of
lead cable to attach the probe to the integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at the probe. Its patented
solid-state construction allows the PHL probe to respond
to most liquid hydrocarbons but ignore vapors, thus virtually
eliminating false alarms due to vapors. PHL is responsivve
to a broad range of fuels and solvents. The probe resets
quickly after removal from exposure to most volatile hydrocarbons.
3.PHFW
- Monitor well probe
The PHFW monitoring well probe can easily be connected
into a PAL-AT cable "sensor string" providing
increased utilization of that PAL-AT capabilities. Each
assembly increases a probe integrator with 60 feet (18m)
of jumper cable to connect to the sensing string, and
20 feet (6m) of lead cable to attach the float switch
to the probe integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at that probe. The TankWatch
probe includes a junction box and contact adaptor in lieu
of the probe integrator.
The
PHFW is designed for use in 4 inch (100mm) monitoring
wells where the sensor can hang vertically, extending
into the water table to the bottom of the well. A weight
attached to the sensor keeps it taut. The sensor filament
responds to contact with selected hydrocarbons floating
on the water by breaking, and/or releasing the weight,
activating a switch. The probe is easily reset by replacing
the filament.
4.PHFW-M
- Monitor well probe
The PHFW-M probes are designed for use in applications
such as manholes and fuel pits, where the sensor cable
must detect hydrocarbons within .25 inch (6.5mm) of the
bottom of the monitored area. If water enters the monitored
area any fuel leaks will float on the water and be detected
by the sensor. The probe's operation is identical to the
PHFW probe and it includes a length of slotted PVC pipe
to mount the probe.
5.PFS
- Float Switch
The PFS float switch can easily be connected into a PAL-AT
cable "sensor string" providing increased utilization
of the PAL-AT capabilities. Each assembly includes a probe
integrator with 60 feet (18m) of jumper cable to connect
to the sensing string, and 20 feet (6m) of lead cable
to attach the float switch to the probe integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at the probe. The TankWatch
probe includes a junction box and contact adaptor in lieu
of the probe integrator.
The
PFS is a hermetically sealed reed float switch which signals
the presence of liquids. The probe resets immediately
after the liquid drops below the activation level.
6.PSTV
- Float Switch
The PSTV float switch can easily be connected into a PAL-AT
cable "sensor string" providing increased utilization
of the PAL-AT capabilities. Each assembly includes a probe
integrator with 60 feet (18m) of jumper cable to connect
to the sensing string, and 20 feet (6m) of lead cable to
attach the float switch to the probe integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at the probe. The TankWatch
probe includes a junction box and contact adaptor in lieu
of the probe integrator.
The
PSTV is a hermetically sealed reed float switch which
signals the presence of liquids. It is designed to fit
into a double-walled tank's 2" standpipe. The probe
resets immediately after the liquid is removed.
7.PTHL
- High level float switch
The PTHL float switch can easily be connected into a PAL-AT
cable "sensor string" providing increased utilization
of the PAL-AT capabilities. Each assembly includes a probe
integrator with 60 feet (18m) of jumper cable to connect
to the sensing string, and 20 feet (6m) of lead cable
to attach the float switch to the probe integrator.
The
unique design of the PAL-AT probe integrator eliminates
the need for additional power at the probe. The TankWatch
probe includes a junction box and contact adapter in lieu
of the probe integrator.
The
PTHL is a hermetically sealed reed float switch which
signals the presence of liquids. It is designed to be
a high level alarm for single and double walled tanks.
Typically, the probe is located to activate when the tank
is 90% full. The probe resets immediately after the liquid
drops below the activation level.
PermAlert
Leak Detection/Location Products
If your browser supports internal links, click onto the
product name for more information, or scroll down the
page to read more about our products in this category
PAL-AT
- microprocessor-based leak detection location system
for piping and stand-alone applications
PALCOM
- remote monitoring software for the PAL-AT system
FluidWatch
- monitors water leaks for small areas
TankWatch-
monitors organic liquid and water leaks in the interstitial
space of tanks as well as float switches
Sensor Cables - application specific coaxial cables
for PermAlert's leak detection/location systems. This
link leads you to a new Web page.
Probes - application specific probes and float switches
for PermAlert's leak detection/location systems. This
link leads you to a new Web page.
PAL-AT®
1.PAL-AT is a patented, sophisticated microprocessor system
with multi-sensing and remote monitoring capabilities.
Its advanced technology provides dependable around the clock
surveillance of all monitored areas. PAL-AT models can monitor
up to eight identical or separate sensing zones each having
up to 5,000 feet of sensor cable. (Call PermAlert for distances
over 5,000 feet.) Each sensor cable can be integrated with
liquid probes and float switches for the monitoring of single-
and/or double-wall piping and tanks. The PAL-AT system permits
cost effective installation of complex systems, with its
ability to integrate different cable types and probes. This
efficiency allows the system to monitor for leaks in complex
piping systems, tanks, subfloors and other sensitive work
areas.
The
extended range systems will allow monitoring over 10,000
feet on a single sensor string. PAL-AT is U.L. listed
and FM approved to provide connections for intrinsically
safe sensor circuits for use in Class 1, Division 1, Groups
C and D hazardous locations when used with PAL-AT cables
and probes. The system has been tested by a Third Party
in accordance with U.S. EPA Guidelines.
Product Features
Locates multiple leaks without loss of accuracy
or sensitivity
Locates breaks and shorts
Stores information with time and date
User friendly RS-232 serial port
Accepts probe and cable sensors in one sensor string
One cable for all liquids or multiple cables for
differentiation (user's option)
AT40K and 80K monitors up to eight separate cable
strings when equipped with Cable Expansion Modules
U.L. listed and FM approved to provide intrinsically
safe sensor cable output circuits for Class 1, Division
1, Groups C & D Hazardous Locations.
PALCOM® Central Point Monitoring
Software
The PALCOM software (available in both Windows and DOS
versions) can centrally monitor up to 254 PAL-AT monitoring
units. The software can continuously monitor the status
and/or remotely operate each PAL-AT system. The archive
feature keeps a record of all system events. Furthermore,
should a leak occur, PALCOM has an optional patented Graphic
Locator System (GLS) that displays the location of the
leak on a CAD drawing.
Compliance
for PAL-AT and PALCOM
The PAL-AT Leak Detection/Location System and PALCOM Communication
Software System comply with the following definition of
year 2000 compliance:
The
ability for continued normal use of the System, such that
neither the performance nor the functionality of the system
will be affected by any changes to the date values caused
by the arrival of the year 2000.
In
particular:
1.No value for current date will cause any interruption
of the system. 2.There is no manipulation of time-related
data. The date/time information is used for history logging
in the archives, which stores the last 900 events. 3.Leap
year is included in the internal workings of the clock.
4.Date elements are represented without a century, but
there are not manipulations involving the date element.
FluidWatch®
The FluidWatch Leak Detection Monitoring Unit is engineered
to monitor small areas for water leaks. Typical applications
include unmanned equipment rooms, small raised floor areas
and small tanks. The system continuously monitors the capacitance
of the sensor cable and detects changes. Seconds after the
coaxial sensor cable contacts water or water-based liquids,
the unit enters into alarm. The sensor cable can be quickly
dried in place after the leak is cleaned up and the system
is back on-line.
FluidWatch
uses an LED "traffic light" display to indicate
status: green - normal; yellow - break; and red - leak.
An audible alarm and two 250 VAC, 10A, SPDT activate relays
when either a leak or break occurs. There are two operator
buttons, one to test the system and the other to silence
the alarm.
Internal
jumpers are used to enable alarm silencing, to select
cable sensitivity and to enable automatic silencing upon
return of the system to normal conditions.
Product
Features Senses water-based liquids within seconds
of contact Sensitivity from several inches to several
feet Durable sensor cable Available in three
different sensor length; 50 ft., 75 ft., and 100 ft. (15m,
30m, and 45m) Comes in a kit, complete with 25 ft.
(7.5m) of jumper cable, sensor cable, cable clips and
cable tags
TankWatch®
TankWatch PHMS Single Channel and PHM 10 Multi Channel
probe monitoring units are engineered to meet a broad range
of customer needs. The multi-channel system can be configured
from one to 10 channels, with each channel capable of monitoring
one dual probe or two single probes. The multi-channel modular
design allows expansion to ten (10) channels by plugging
in channel expansion cards and connecting probes. Modular
construction permits plug-in pull-out service ease.
TankWatch
employs an understandable "traffic light" display
for status indication: green - normal; yellow - break;
and red - leak. The unit enters into an alarm mode on
any red or yellow condition, activating an audible alarm.
A leak activates the system relay for external alarm or
control functions. There are two operator buttons. One
is used to test the system and other other to silence
the alarm. This silence button can be disabled, via an
internal jumper, to prevent unauthorized silencing.
TankWatch
units are equipped with normally energized, 10 A, 240
VAC, DPDT relays; one relay for PHMS, four relays for
PHM10. Any or all relays can be field set to respond to
leaks. The alarm console can be located up to 5,000 feet
from the probes. The system relays can activate an optional
remote alarm.
Patented
compact probes for TankWatch are solid-state design and
respond in seconds, after contact with organic liquids
or water. Hydrocarbon fumes or vapor have no effect, thereby
virtually eliminating false alarms. There are probes available
for monitoring ground water, brine levels in underground
storage tanks and float switches for high/low level.
TankWatch
can also monitor any switch (float switch, thermostat,
high level switch, etc.) that is connected to the optional
contact adapter.
Product
Features
Solid state probe sensor technology
Sensing of organic liquids and water within seconds
of contact
Vapor and gases are ignored
Remote monitoring capabilities
Broad detectable range of organic liquids
Monitors optional switches
U.L. Listed to provide intrinsically safe sensor
output circuits for Class 1, Division 1, Groups C &
D Hazardous Locations
U.S. Patent 4,855,706
Modified NEMA 12 Enclosure